Diesel Generator Fuel Consumption Chart
This chart approximates the fuel consumption of a diesel generator based on the size of the generator and the load at which the generator is operating. Please note that this table is intended to be used as an estimate of how much fuel a generator uses during operation and is not an exact representation due to various factors that can increase or decrease the amount of fuel consumed.
If you have questions, already know your requirements, or are interested in purchasing please contact us, or browse our inventory of diesel and natural gas generators. Hardy Diesel has an extensive inventory of new generators, transfer switches, generators ends and generator set accessories from leading manufacturers known for quality, dependability and product support.
Chart numbers represent estimated gallons per hour consumed (Gallons/Hour, Gal/Hour).
Generator Size (kW) | 50 Percent Load | 75 Percent Load | 100 Percent Load |
---|---|---|---|
8 | 0.39 gal/hr | 0.54 gal/hr | 0.69 gal/hr |
10 | 0.53 gal/hr | 0.65 gal/hr | 0.88 gal/hr |
15 | 0.69 gal/hr | 0.94 gal/hr | 1.22 gal/hr |
20 | 0.90 gal/hr | 1.30 gal/hr | 1.60 gal/hr |
30 | 1.80 gal/hr | 2.40 gal/hr | 2.90 gal/hr |
40 | 2.30 gal/hr | 3.20 gal/hr | 4.00 gal/hr |
60 | 2.90 gal/hr | 3.80 gal/hr | 4.80 gal/hr |
75 | 3.40 gal/hr | 4.60 gal/hr | 6.10 gal/hr |
100 | 4.10 gal/hr | 5.80 gal/hr | 7.40 gal/hr |
125 | 5.00 gal/hr | 7.10 gal/hr | 9.10 gal/hr |
135 | 5.40 gal/hr | 7.60 gal/hr | 9.80 gal/hr |
150 | 5.90 gal/hr | 8.40 gal/hr | 10.90 gal/hr |
175 | 6.80 gal/hr | 9.70 gal/hr | 12.70 gal/hr |
200 | 7.70 gal/hr | 11.00 gal/hr | 14.40 gal/hr |
230 | 8.80 gal/hr | 12.50 gal/hr | 16.60 gal/hr |
250 | 9.50 gal/hr | 13.60 gal/hr | 18.00 gal/hr |
300 | 11.30 gal/hr | 16.10 gal/hr | 21.50 gal/hr |
350 | 13.10 gal/hr | 18.70 gal/hr | 25.10 gal/hr |
400 | 14.90 gal/hr | 21.30 gal/hr | 28.60 gal/hr |
500 | 18.50 gal/hr | 26.40 gal/hr | 35.70 gal/hr |
600 | 22.00 gal/hr | 31.50 gal/hr | 42.80 gal/hr |
750 | 27.40 gal/hr | 39.30 gal/hr | 53.40 gal/hr |
Why do some engines burn more fuel than others at the same load?
The biggest factor is fuel consumption related to cooling fans and water pumps of various generator sets. For that reason, a 100kW generator will burn more fuel at 10kW than a 10kW generator set.
Can I believe the manufacturer’s spec sheets when it comes to fuel consumption?
It depends. There are no established standards or regulations governing how manufacturers measure fuel consumption for generator sets or engines. Additionally, there are no standard conditions in which these tests should be performed, therefore fuel consumption numbers reported can vary from brand to brand.